6 Parameters

6.1 Parameter Group O-##

O-01 Control Site

Option:

Function:

The setting in this parameter overrides the settings in par. O-50 Coasting Select to par. O-56 Preset Ref-
erence Select
.

[0] *

Digital and ctrl.word

Control by using both digital input and control word.

[1]

Digital only

Control by using digital inputs only.

[2]

Controlword only

Control by using control word only.

O-02 Control Word Source

Select the source of the control word: one of two serial interfaces or four installed options. During initial power-up, the frequency converter automatically sets
this parameter to Option A [3] if it detects a valid network option module installed in slot A. If the option is removed, the frequency converter detects a change
in the configuration, sets par. O-02 Control Word Source back to default setting Drive RS485, and the frequency converter then trips. If an option is installed
after initial power-up, the setting of par. O-02 Control Word Source will not change but the frequency converter will trip and display: Alarm 67 Option
Changed
.
This parameter cannot be adjusted while the motor is running.

Option:

Function:

[0]

None

[1]

Drive RS485

[2]

Drive USB

[3] *

Option A

[4]

Option B

[5]

Option C0

[6]

Option C1

O-03 Control Word Timeout Time

Range:

Function:

1.0 s*

[0.1 - 18000.0 s]

Enter the maximum time expected to pass between the reception of two consecutive messages. If this
time is exceeded, it indicates that the serial communication has stopped. The function selected in
par. O-04 Control Word Timeout Function will then be carried out. The time-out counter is triggered by a
valid control word.