EN-13 Link Speed

Option:

Function:

Forces the link speed for each port in 10 or 100 Mbps. If par. EN-12 is set to: ON, this parameter is read
only and displays the actual link speed. “None” is displayed if no link is present.

[0] *

None

[1]

10 Mbps

[2]

100 Mbps

EN-14 Link Duplex

Option:

Function:

Forces the duplex for each port to Full or Half duplex. If par. EN-12 is set to: ON, this parameter is read
only.

[0]

Half duplex

[1] *

Full duplex

EN-21 Process Data Config Write

Range:

Function:

[[0 - 9] PCD read 0 - 9]

Configuration of readable process data.

NB!
For configuration of 2-word (32-bit) parameter read/write, use 2 consecutive arrays in par. EN-21 and EN-22.

EN-22 Process Data Config Read

Range:

Function:

[[0 - 9] PCD read 0 - 9]

Configuration of readable process data.

EN-28 Store Data Values

Option:

Function:

This parameter activates a function that stores all parameter values in the non-volatile memory (EEPROM)
thus retaining parameter values at power-down.
The parameter returns to “Off”.

[0] *

Off

The store function is inactive.

[1]

Store All set-ups

All parameter value will be stored in the non-volatile memory, in all four setups.

EN-29 Store Always

Option:

Function:

Activates function that will always store received parameter data in non-volatile memory (EEPROM).

[0] *

Off

[1]

On

Modbus TCP

39

6