Modbus tcp – GE Industrial Solutions AF-600 FP OPCMBTCP Modbus TCP Option User Manual

Page 19

Advertising
background image

After selecting “OK” the network “GE” should show up under Networks and by selecting the Network, the main configuration page will be shown.

In this menu the following settings have to be made:

Menu

Menu point

Setting

Model Family

Model Family

NOE 0100, NOE 110

Model Utilities

IO Scanning

YES

Global Data

NO

Address Server

NO

IP address configuration

Configured/From a server

Configured

IP address

192.168.001.020

Subnetwork mask

255.255.255.0

Gateway address

0.0.0.0

Ethernet Configuration

Ethernet Configuration

Ethernet II

In the IP Configuration tab, the “Configured” bottom has to be selected, and the IP address and Subnetwork mask has to be filed out. In this example the address
192.168.1.20 is used as the address for the master.

The step assigns the protocol to the scanner, which is done by selecting the scanner and selecting the “Function” menu and enables the Ethernet by selecting “ETH
TCP IP” This brings up the Net Link menu, where “GE” has to be selected. At this time the “GE” Protocol is assign to the Scanner and the last step is to configure the
scanner to read and write holding registers of the AF-650 GP.

Modbus TCP

18