O-04 Control Word Timeout Function

Select the time-out function. The time-out function activates when the control word fails to be updated within the time period specified in par. O-03 Control
Word Timeout Time
.

Option:

Function:

[0] *

Off

Resumes control via serial bus (Network or standard) using the most recent control word.

[1]

Freeze output

Freezes output frequency until communication resumes.

[2]

Stop

Stops with auto restart when communication resumes.

[3]

Jogging

Runs the motor at JOG frequency until communication resumes.

[4]

Max. speed

Runs the motor at maximum frequency until communication resumes.

[5]

Stop and trip

Stops the motor, then resets the frequency converter in order to restart: via the network, via the reset
button on the Keypad or via a digital input.

[7]

Select setup 1

Changes the set-up upon reestablishment of communication following a control word time-out. If com-
munication resumes causing the time-out situation to disappear, par. O-05 End-of-Timeout Function de-
fines whether to resume the set-up used before the time-out or to retain the set-up endorsed by the time-
out function.

[8]

Select setup 2

See [7] Select setup 1

[9]

Select setup 3

See [7] Select setup 1

[10]

Select setup 4

See [7] Select setup 1

NB!
The following configuration is required in order to change the set-up after a time-out:
Set par. K-10 Active Set-up to [9] Multi set-up and select the relevant link in par. K-12 This Set-up Linked to.

O-05 End-of-Timeout Function

Option:

Function:

Select the action after receiving a valid control word following a time-out. This parameter is active only
when par. O-04 Control Word Timeout Function is set to [Set-up 1-4].

[0]

Hold set-up

Retains the set-up selected in par. O-04 Control Word Timeout Function and displays a warning, until
par. O-06 Reset Control Word Timeout toggles. Then the drive resumes its original set-up.

[1] *

Resume set-up

Resumes the set-up active prior to the time-out.

O-06 Reset Control Word Timeout

This parameter is active only when Hold set-up [0] has been selected in par. O-05 End-of-Timeout Function.

Option:

Function:

[0] *

Do not reset

Retains the set-up specified in par. O-04 Control Word Timeout Function, following a control word time-
out.

[1]

Do reset

Returns the frequency converter to the original set-up following a control word time-out. The frequency
converter performs the reset and then immediately reverts to the Do not reset [0] setting