13 - 4 Troubleshooting Millennium Systems

Issue 5 September 2011

BATT Alarm LED

Table 13-B: Battery Alarms

(See Figure 12-5)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)

BATT

CRIT

Very Low Voltage

--

Occurs in an
operating system
following an
extended
commercial ac
power outage,
during which the
batteries are
providing power
for the system and
the system voltage
is approaching the
user-defined low
limit.

1. If commercial ac power

is present but the
system voltage remains
low, call technical
support.

2. Investigate other alarms

that may be present
(rectifier-related alarms
and the AC Fail alarm
may also occur during
the fault condition).

BATT*

*Alarm
must be
configured
to turn on
the BATT
LED; not a
factory
default.

MAJ

Contactor 1 Open

Red LED on
contactor
drive board
is lit.

Contactor is open:
•Open has been

initiated by
controller.

•Open has been

initiated manually.

1. Follow instructions on

the label adjacent to the
contactor drive board
(see Figure 12-5).

2. If the problem is not

corrected, call technical
support.

BATT*

*Alarm
must be
configured
to turn on
the BATT
LED; not a
factory
default.

MAJ

Contactor 1 Fail

--

Contactor or drive
board has failed.

Call technical support.

BATT

MIN

Open String

Alarm LED
on battery
fuse panel is
lit.

Battery fuse has
operated.

Replace the operated fuse.

BATT

MIN

Low Reserve Time --

Controller has
calculated that
batteries are low.

Call technical support.