Galaxy Power System 4848/100 with Dual Rectifier Shelf

13 - 8 Troubleshooting Millennium Systems

Issue 5 September 2011

CTRL

MAJ

Controller Fail

--

•BSH failure
•BSJ failure
•Option board

failure

•Display failure
•BIC failure

1. Strap K1, K2, K3 on BLJ

from “C” to “R” prior to
replacing BIC. See
Figure 8-2.

2. Replace BIC.

CTRL

MAJ

Circuit Pack Fail

--

See “Controller
Fail”.

See “Controller Fail”.

CTRL

MAJ

Controller Fuse

--

Fuse has operated.

Replace the controller fuse
labeled F2 (intelligent
power).

CTRL

MAJ

Alarm Battery
Supply Fuse

--

Fuse has operated.

Replace the controller fuse
labeled F5 (alarm battery
supply).

CTRL

MAJ

Remote Peripheral
Fuse

--

Fuse has operated.

Replace the controller fuse
labeled F1 (option power).

CTRL

MAJ

Sense/Control
Fuse

--

Fuse has operated.

Replace the controller fuse
labeled F4 (voltage sense).

CTRL

MAJ

Bay Interface ID
Conflict

--

Two or more bay
interface cards
(BICs) have the
same ID number.

Following instructions
printed on the label over the
BIC, adjust the DIP
switches to change the ID
number.

CTRL

MAJ

Major
Communication
Fail Alarm

Blinking
ALM LED
on rectifiers
or
red LED on
BIC

Loss of
communication
with controller:
•Defective

interface from
BIC or multiple
rectifiers to
controller

•Internal failure of

controller, BIC, or
multiple rectifiers

1. Verify that the controller

is powered and operating
correctly.

2. If there are no controller

alarms, replace the
equipment that has lost
communication.

3. If the problem is not

corrected, call technical
support.

Table 13-C: Controller Alarms (Continued)

(See Figures 12-2 and 12-3)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)