GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual

Page 112

Advertising
background image

Galaxy Power System 4848/100 with Dual Rectifier Shelf

13 - 14 Troubleshooting Millennium Systems

Issue 5 September 2011

RECT

MIN

Excess System
Drain

None

None

System load
exceeds shunt
rating.

Call technical support.

RECT

MIN

Limited Recharge

None

None

Rectifier
capacity has
been exceeded.

Install more rectifiers.

RECT

MIN

Rectifier Fail

ALM

ILC

Rectifier not
fully seated.

1. Place the ac circuit

breaker for the
rectifier in the OFF
position.

2. Remove the

rectifier from the
shelf.

3. Wait for 30 seconds

or until all front
panel display LEDs
have extinguished.

4. Replace the

rectifier.

5. Return the ac

breaker to the ON
position.

6. Place the rectifier

ON/STBY switch
into the ON
position.

7. If the problem is not

corrected, replace
the rectifier with a
new one.

Table 13-E: Rectifier Related Alarms (Continued)

(See Figures 12-4 and 12-6)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)

Advertising