Removing a rectifier, Replacement procedures, continued – GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual

Page 78

Advertising
background image

Galaxy Power System 4848/100 with Dual Rectifier Shelf

11 - 6 Maintenance and Replacement

Issue 5 September 2011

Replacement Procedures, continued

Removing a

Rectifier

Removing a Rectifier

Step

Action

1

Set power switch to STBY.

2

Turn OFF ac circuit breakers.

3

Turn OFF output circuit breaker on rectifier.

4

Wait 5 minutes to allow capacitors to discharge.

5

Using a 5mm Allen-head “T” wrench, slowly turn the locking
screw counterclockwise to release the rectifier from the shelf.

6

Slowly slide rectifier from shelf.

Caution

Rectifier is heavy (37 pounds).

Do not rest rectifier on faceplate or rear chassis; damage to
faceplate and/or rear busbars will occur, rendering the unit
unusable.

7

If the rectifier is not going to be replaced immediately, retire the
active CMA (Communications Fail - Minor) against that
rectifier ID by using the following path on the Configuration
menu on the front display of the plant controller:
Menu -> CONFIG -> RECT MNGR (Basic Controller)
or
Menu -> CONFIG -> RECT MNGR -> RECT OPER (Intel
Controller)
Move to the Field RMOVE RECT and use the (+) key to input
the Rectifier ID of the removed rectifier. Press Enter to clear the
alarm.

8

If the removal of the rectifier results in a vacant rectifier
position below or beside the top installed rectifier in this
cabinet, it must be replaced immediately or the vacated position
must be occupied by a Rectifier Shelf Cover or Air Dam.

Rectifier Shelf Cover Covers both left and right rectifier
(848680211)

positions

Air Dam

Covers the left or right rectifier

(

CC848809178

)

position

Advertising