Galaxy Power System 4848/100 with Dual Rectifier Shelf

Issue 5 September 2011

Troubleshooting Millennium Systems 13 - 15

BD and RM Alarm

LEDs, or No LED

Table 13-F: Miscellaneous Alarms

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)

BD

MAJ

Battery on
Discharge

Rectifiers
may say
ACF.

Temporary
condition that may
be associated with
other alarms

Call technical support.

RM

MIN

Module Failure

Green LED
on RPM will
not blink.

Remote Peripheral
Module has failed.

Call technical support.

RM

MIN

Measurement Out
of Range

--

•Data being sensed

exceeds remote
peripheral
module’s
capability.

•Remote peripheral

module has failed.

Call technical support.

None

MAJ

Auxiliary Major

Auxiliary
equipment
may have
alarm.

Problem with
operation of
auxiliary equipment

Call technical support.

None

MIN

Auxiliary Minor

Auxiliary
equipment
may have
alarm.

Problem with
operation of
auxiliary equipment

Call technical support.

None

None

None

•STBY LED

on rectifier
is lit.

•TR on

rectifier
display

Remote transfer:
•Rectifier is in

STBY.

Remove the remote
standby command issued
by the controller.

None

None

None

Red LED is
lit on some
battery
contactor
drive
boards,
while green
LED is lit on
others.

If a green LED is lit
despite a contactor
open command
issued by the
controller, the drive
card or the
contactor has failed.

Call technical support.