Low voltage load disconnect, Figure 12-9: low voltage load disconnect contactor, Control switches – GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual

Page 97: Reference figures, continued

Advertising
background image

Galaxy Power System 4848/100 with Dual Rectifier Shelf

Issue 5 September 2011

Troubleshooting Preparations 12 - 11

Reference Figures, continued

Low Voltage Load

Disconnect

The EBV low voltage load disconnect (LVLD) contactor control board
is mounted on the right side of the cabinet, as shown in Figure 12-9.

The manual contactor control switch (SW300) is not meant to be used
to permanently override the LVLD function. It is only to be used
temporarily while servicing or testing the equipment.

Figure 12-9: Low Voltage Load Disconnect Contactor

Control Switches

Note: Switch should be in the
down position for normal operation.

Red Light

Yellow Light

Green Light

UP POSITION FORCES
CONTACTOR CLOSED

REMOTE CONTROL
ENABLED

CONTROLLER SIGNAL
ERROR DETECTED

CONTROLLER SIGNAL
OPENED CONTACTOR

GREEN LIGHT

YELLOW LIGHT ONLY

RED AND YELLOW LIGHT

LOAD DISCONNECT FEATURE IS NOT

FOR USE IN BATTERYLESS SYSTEMS

REMOTE
CONTROL
OVERRIDE
SWITCH

Control switch mounted
on right side of cabinet.