Galaxy Power System 4848/100 with Dual Rectifier Shelf

9 - 4 Specifications

Issue 5 September 2011

Rectifiers

Table 9-B: 595LT Series S2:x Rectifier Specifications

Electrical

Output Voltage

52Vdc typical

Output Voltage Adjustment

44-58Vdc float/boost

Regulation (with controller)

±0.5%

Output Current

595LTA

595LTB

220A

0°C to 40°C

0°C to 37°C

At 50°C

200A

200A

High Voltage Shutdown
(selected by controller)

Float/boost 44-60Vdc (56Vdc default)

Backup High Voltage Shutdown

Float/boost 59-60Vdc (59.5Vdc nominal)

Output AC Ripple

100mVrms

Output Noise - Voiceband

55dBrnC

Current Limit Set Point

60Adc - 220Adc

595LTA Rectifier

595LTB Rectifier

Nominal Input Voltage (3-wire plus ground)

380 - 480 Vac

200 - 240 Vac

Input Voltage Range (per phase)

320 - 530 Vac

176 - 275Vac

Input Current

Specified

Rated Maximum

Typical Maximum

20A at 480Vac

40A at 208Vac

25A at 380Vac

35A at 240Vac

30A

50A

22A at 320Vac

41A at 176Vac

19A at 380Vac

36A at 200Vac

15A at 480Vac

33A at 208Vac
30A at 240Vac

Frequency Range

47 - 63 Hz

Power Factor

0.99 from 50% to 100% load

Total Harmonic Distortion

<5% from 50% to 100% load

AC Surge Protection: It is important that ac surges reaching rectifiers do not exceed the capacity of the rectifier
internal surge protection. Protection must be provided external to the GPS system to limit surge energy reaching
the rectifiers. Site surge protection must be coordinated with rectifier internal surge protection and must clamp at
a lower voltage than the rectifier internal protection. The internal protection voltage and current characteristics of
the rectifiers are as follows:

595LTA
Phase to Phase

MOV Conduction

Voltage

Current

625 Vac (RMS)

0 A

940 Vpeak

1 mA

1650 Vpeak

100 A

595LTB
Phase to Phase

MOV Conduction

Voltage

Current

320 Vac (RMS)

0 A

462 Vpeak

1 mA

810 Vpeak

100 A