GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual

Page 111

Advertising
background image

Galaxy Power System 4848/100 with Dual Rectifier Shelf

Issue 5 September 2011

Troubleshooting Millennium Systems 13 - 13

RECT

MIN

Rectifier Fail

ALM

SEN

Thermal sensor
failure:
•Internal rectifier

failure

1. Place the ac circuit

breaker for the
rectifier in the OFF
position.

2. Remove the

rectifier from the
shelf.

3. Wait for 30 seconds

or until all front
panel display LEDs
have extinguished.

4. Replace the

rectifier.

5. Return the ac

breaker to the ON
position.

6. Place the rectifier

ON/STBY switch
into the ON
position.

7. If the problem is not

corrected, replace
the rectifier with a
new one.

RECT

MIN

Rectifier Fail

FAN
ALM

None

Fan failure

Replace the fan in the
rectifier.

RECT

MIN

Manual Off

STBY

Blank

Rectifier has
been manually
turned off.

Turn rectifier on.

RECT

MIN

External Transfer
Shutdown

STBY

TR

System is
operating on
external engine.

No action required.

RECT

MIN

High Float Voltage None

None

Configuration
problem

Call technical support.

RECT

MIN

Excess Rectifier
Drain

None

None

Internal rectifier
fault

Replace rectifier.

Table 13-E: Rectifier Related Alarms (Continued)

(See Figures 12-4 and 12-6)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)