Replacement procedures, continued – GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual

Page 80

Advertising
background image

Galaxy Power System 4848/100 with Dual Rectifier Shelf

11 - 8 Maintenance and Replacement

Issue 5 September 2011

Replacement Procedures, continued

Replacing the Rectifier Fan Assemblies, continued

Step

Action

6

Remove the fan cable clamps.

7

Carefully unplug the fan connectors (2). Fan connectors are
keyed and can be loosened by inserting a screwdriver into the
slotted side of the connector and gently prying the fan-side
connector loose.

8

Remove the fans by removing the fan screws (8).

9

Install the new fans in position as shown in Figure 11-2 by
installing the fan screws (8).

10

Position the fan cables as shown in Figure 11-2.

11

Replace the fan cable clamps.

Caution

Place faceplate ground wire terminal under fan cable

clamp as shown in Figure 11-2.

12

Replace the faceplate by installing the faceplate screws (4).

13

Install the rectifier, following the “Installing or Replacing a
Rectifier” procedure in this section.

14

Test replaced rectifiers using the “Testing Additional Alarms
After Replacement of Rectifiers” procedure in this section.