Galaxy Power System 4848/100 with Dual Rectifier Shelf

Issue 5 September 2011

Troubleshooting Preparations 12 - 7

Reference Figures, continued

Low Voltage

Battery Disconnect

The low voltage battery disconnect (LVBD) feature consists of a
contactor, circuitry on the BJN board, and associated wiring. Control of
the contactor is dictated by the BJN contactor control board and the
controller.

Figure 12-5: Low Voltage Battery Disconnect

Contactor Control Switches

Red Light

Yellow Light

Green Light

CONTACTOR DRIVE BOARD

SW

SW

SW

BOTH SWITCHES DOWN
FORCES CONTACTOR OPEN

CONTACTOR OPEN

CONTACTOR OPEN INITIATED

DOWN FORCES

CONTACTOR CLOSED

REMOTE CONTROL ENABLED

Note: All switches should be in the
up position for normal operation.