GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual

Page 109

Advertising
background image

Galaxy Power System 4848/100 with Dual Rectifier Shelf

Issue 5 September 2011

Troubleshooting Millennium Systems 13 - 11

RECT

MIN

Rectifier Fail

ALM

TA

Thermal alarm:
•Excessive

ambient
temperature

•Internal rectifier

failure

1. Verify that there is

no obstruction of
the fan inlet.

2. Toggle the ON/

STBY switch into
the STBY position
and then back into
the ON position.

3. If the problem is not

corrected, replace
the rectifier.

RECT

MIN

Rectifier Fail

ALM

CB

Circuit breaker
alarm:
•DC output

circuit breaker
open

•Internal rectifier

failure

1. Toggle the ON/

STBY switch into
the STBY position;
toggle the DC
output circuit
breaker into the
OFF position and
then into the ON
position. Return the
ON/STBY switch to
the ON position.

2. If the problem is not

corrected, replace
the rectifier.

Table 13-E: Rectifier Related Alarms (Continued)

(See Figures 12-4 and 12-6)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Rectifier

LED

Rectifier

Display

Possible

Problem(s)

Possible Solution(s)

Advertising