User interface and display, Front panel, Default display – GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual

Page 32

Advertising
background image

Galaxy Power System 4848/100 with Dual Rectifier Shelf

3 - 2 Galaxy Millennium Controller

Issue 5 September 2011

User Interface and Display

Front Panel

The control panel displays alarm and status indicators and provides test
jacks to monitor the system output. Keys are provided for interacting
with various menus that configure and monitor the system. The
controller menus can be viewed in either English or Spanish.

The user’s primary interface with the controller is a panel that includes
a backlit LCD front panel display, two rows of LEDs, test jacks, and an
array of simple pushbutton controls. See Figure 3-1.

Figure 3-1: Galaxy Millennium Controller Front Panel

Galaxy Millennium Controller

Alarm Status

Critical

Escape

Help

Enter

Menu

Equipment Status

AC System

Battery

Controller

Distribution

Rectifier

Remote
Modules

Major

Minor

Normal

Battery on
Discharge

V

Default Display

The default display shows basic plant status. The controller returns to
this display three minutes after the last time a key is pressed. The default
screen display is similar to the following: The first line shows the
number of alarms (0) and warnings (0) present in the system, the date
and time. The next two lines show the plant voltage and the plant load.
The last line shows the plant mode, which can be FLOAT, BOOST, STC
(Slope Thermal Compensation), BTP (Battery Thermal Protection, a
boost mode that offers protection against thermal runaway), or BATT
TEST mode.

The information on the screen is updated automatically approximately
every two seconds.

Advertising