Galaxy Power System 4848/100 with Dual Rectifier Shelf

Issue 5 September 2011

Troubleshooting Millennium Systems 13 - 7

CTRL

MAJ

Controller Fail

--

•BSH failure
•BSJ failure
•Option board

failure

•Display failure
•BIC failure

Check the option boards
(modem and data switch) to
see if the green LED is
extinguished and the yellow
LED is lit. If so, perform
the following steps:
1. Press the SW201 reset

switch on the top of the
BSJ board. (This circuit
has an automatic restart,
which will try three
times to restart the
microprocessor.) If the
BSJ is not present, press
the reset switch on the
top of the BSH board.

2. If the diagnostics did not

pass, or if the problem
recurs, replace the failed
option board.

CTRL

MAJ

Controller Fail

--

•BSH failure
•BSJ failure
•Option board

failure

•Display failure

•BIC failure

If the front panel LCD
module, LEDs, or switches
fail, perform the following
steps:
1. Verify that the ribbon

cable from the BSH
board to the display is
not cut, abraded, or
otherwise mangled.
Replace the cable if
damaged.

2. Press SW200 to reset the

BSH board.

3. If the LCD module is

still not operating,
replace the LCD module;
if the switches and LEDs
are still not operating,
replace the BSH board.

Table 13-C: Controller Alarms (Continued)

(See Figures 12-2 and 12-3)

Controller

LED

Controller

Alarm

Status

Millennium

Controller Display

Other

Indication(s)

Possible Problem(s)

Possible Solution(s)

Advertising