GE Industrial Solutions GPS 4848_100 Users Guide (dual rectifier shelf) User Manual

Page 64

Advertising
background image

Galaxy Power System 4848/100 with Dual Rectifier Shelf

9 - 2 Specifications

Issue 5 September 2011

Physical

Width, Depth

600 mm, 600 mm (23.6 in. x 23.6 in.)

Weight (approximate, per cabinet)

250 kg (551 lbs.)

Height (cabinet only)

2134 mm (84.0 in.)

Height (cabinet with link bus bar)

2274 mm (89.5 in.)

Environmental

Heat Release, per cabinet

(including 1% cabinet loss)

Number of Rectifiers

4
5
6
7
8

10
12
14

per Rectifier

at 54Vdc, 200Adc

595LTA S2:x

595LTB S2:x

2,240W (7,700 BTU / hr)

2,480W

(8,500 BTU / hr)

2,800W (9,600 BTU / hr)

3,100W

(10,600 BTU / hr)

3,360W (11,500 BTU / hr)

3,720W

(12,700 BTU / hr)

3,920W (13,400 BTU / hr)

4,340W

(14,900 BTU / hr)

4,480W (15,300 BTU / hr)

4,960W

(17,000 BTU / hr)

5,600W (19,200 BTU / hr)

6,200W

(21,200 BTU / hr)

6,720W (23,000 BTU / hr)

7,440W

(25,500 BTU / hr)

7,870W (26,800 BTU / hr)

8,680W

(29,700 BTU / hr)

560W

(1,900 BTU / hr)

620W

(2,120 BTU / hr)

Operating Temperature

0°C to 40°C

Operating Relative Humidity

5% - 95%

Units Per Cabinet with Controller

Rectifiers

595LTA / 595LTB: 0 - 12; 595A / 595B: 0 - 6

Controller

1

Battery Modules

0 - 3

DC Distribution

1 - 6

(maximum of 5 with battery disconnect)

Units Per Cabinet without Controller

Rectifiers

595LTA / 595LTB: 0 - 14; 595A / 595B: 0 - 7

Battery Modules

0 - 1

DC Distribution

1 - 6

(maximum of 5 with battery disconnect)

Table 9-A: Galaxy Power System 4848/100 Specifications (Continued)