3.4 PLACE OF INSTALLATION

The UPS should be installed in a restricted area where only qualified personnel should be admitted.

The place of installation should be clean, dust-free, and provided with proper ventilation or air-
conditioning
.

Verify for sufficient floor load capacity (see Section 3.1.1).

We strongly advice that the ambient temperature should not exceed 68° - 77°F (20° - 25°C), max. 95°F
(35°C). See Section 3.5.

NOTE !

Insufficient space on both sides of the UPS in respect to the wall can cause a
dangerous increase of the internal operating temperature.

Fig. 3.4-1 LP 33U Series positioning

Fig. 3.4-2 LP 33U Series RPA parallel system positioning

LP 33U Series positioning

For easier access in case of maintenance
operation and for a free circulation around
the cabinet, we recommend to maintain the
following minimum distances:
Right & left side:

4”

(100mm)
Rear side:

2”

(50mm)
Top of the UPS: 12”
(300mm)




Right & left side:

4”

(100mm)
Rear side:

2”

(50mm)
Between units:

8”

(200mm)
Top of the UPS: 12”
(300mm)

NOTE !

Operating temperature is very important for valve regulated battery (maintenance
free).
Operation at temperatures higher than 68°F (20°C) will reduce life expectancy.
Respect the prescription of the battery supplier and other local standards.
The installation and cabling of the battery must be done by qualified people.