J2 x1, Jp3 x2, Epo (emergency power off) – GE Industrial Solutions LP 33U Series 10 & 20 kVA Installation Guide User Manual

Page 39

Advertising
background image

Modifications reserved

Page 39/40

OPM_LPS_3UI_10K_20K_1US_V010.doc

Installation Guide LP 33U Series 10 & 20 kVA / S1

EPO (Emergency Power Off)


An external Emergency switch (NC - Normally Closed voltage-free contact) can be connected on

terminals X2 / 1, 2 or connector J2 / 12, 25 of the Customer Interface (see Fig. 4.4.1-1 / X2 & J2).

7

89

1

0

11

22

21

20

19

18
7

J2

X1

2
1

JP3

X2

Fig. 4.4.1-2 PCB Customer Interface

LPS33U

_010-020

_UPS EP

O_01

OFF

Q1

Q2

ON

OFF

ON

F1 F2

F3

F13 F14

F15

F9 F10

F11

1

2

X7

P2 - Mainboard

J28

JP8

Fig. 4.4.1-3 PCB P2 - Mainboard

NOTE !

To enable this function, remove jumper JP3 on the Customer Interface and the
cable on the terminal X2 / 1, 2
(see Fig. 4.4.1-2).
Verify if the cable on the terminal X7 / 1, 2 and jumper JP8 on the control board P2
– Mainboard
are OFF (see Fig. 4.4.1-3).

In a parallel system a separate NC (Normally Closed) contact must be connected
individually to each unit.


When activated, this switch causes the immediate shutdown of booster, battery-charger, inverter; and
the contactors K4, K6 and K7.

NOTE !

This procedure could imply a load shutdown.

When the EPO has been activated, the system must be restored as follows:

Press the push-button EPO (contact on X7 / 1, 2 is closed again).

Press the key O (Inverter OFF – see Section 6.2 of Operational Manual) on the control panel.

Press the key I (Inverter ON – see Section 6.2 Operational Manual) on the control panel.

In case of a Parallel System press the key “O” (Inverter OFF) on the control panel of
each unit connected on the parallel bus and having its output switch Q1 closed.