Installation Guide LP 33U Series 10 & 20 kVA / S1

Access to the terminals for the cable connections

OFF

OFF

ON

ON

A

B

C

Bottom entry cables

C

LPS33U

_010-020

_Connec

tion com

mon_01

Fig. 3.8.1-1 Access to the input / output connections

To access input, output and battery
connections proceed as follows:

• Open the front door “A” of the cabinet.

• Remove the protection panel “B”.

• Remove the plate “C” for bottom cable

entry.

NOTE !

Drill in the plate “C” appropriate holes for cable conduits (max. 4 x 1”1/4”).
Please remove the plate “C” before drilling any wholes.
See Fig 3.8.1-1
for details “C”.


3.8.2

Internal fuse ratings

LP 33U Series internal fuses

The UPS is equipped with rectifier input fuses F1,
F2, F3
and battery fuses F9, F10, F11 and F13, F14,
F15
(only for LP 33U Series / 20 kVA).

In case of replacement the same type and the
same rating must be used (see table below).

Fig. 3.8.2-1 Internal fuses

NOTE !

Rectifier input fuses F1, F2, F3
The fuses must be inserted in the
fuse holder with blown fuse
indicator upwards (see label on
fuse holder).

Fuses type URD

660/690 VAC

Fuses type AJT40

660 VAC

Fuses type AJT40

660 VAC

UPS

F1 - F2 - F3

F9 - F10 - F11

F13 - F14 - F15

(only for LP 33U Series / 20

kVA)

LP 33U Series / 10 kVA

40 A (14 x 51 mm)

40 A (27 x 63 mm)

-

LP 33U Series / 20 kVA

80 A (22 x 58 mm)

40 A (27 x 63 mm)

40 A (27 x 63 mm)