Installation Guide LP 33U Series 10 & 20 kVA / S1

3.9.2

Dual input utility (option)

Fig. 3.9.2-1 Dual input utility (option)

Dual input utility

On request, the UPS can be delivered for dual input
utility
.

Two independent lines (F2 and F3) supply
separately the rectifier and the bypass inputs

With this configuration, when the rectifier-input
fuses are opened, the automatic bypass and the
maintenance bypass are supplied by the other line.


OFF

ON

ON

OFF

L1

-1

L2

-1

L3

-1

N1

L1

L2

L3

N2

RECTIF

IER

LOAD

X2

INPUT

1-

BYPAS

S

INPUT

2-

L1

-2

L2

-2

L3

-2

X1

LOAD

LPS33U

_010-020

_Connec

tion com

mon_01

Fig. 3.9.2-2 Power connections Dual Input Utility

Rectifier input utility
L1-1
= Rectifier Phase A
L2-1 = Rectifier Phase B
L3-1 = Rectifier Phase C
N1 =

Neutral

utility

PE =

Earth

Bypass input utility
L1-2
= Bypass Phase A
L2-2 = Bypass Phase B
L3-2 = Bypass Phase C
(N1 = Neutral

utility)

PE =

Earth

Output load
L1
=

Load

phase

A

L2 =

Load

phase

B

L3 =

Load

phase

C

N2 =

Neutral

load

PE =

Earth

load

Max. rating X1 and X2
terminals: 4 AWG (25mm

2

)

NOTE !

For UPS correct operation, the input utility phase rotation must be clock-wise.
Neutral of rectifier
input and neutral of bypass input must be coming from the
same input bar.
Inside the UPS, all neutrals N1
and N2 are connected together.


Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: Section 3.8.1.


NOTE !

This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.