Installation Guide LP 33U Series 10 & 20 kVA / S1

Wire sizing according to NEC Section 210-20 (a) Table 310-16
Use 167°F (75°C) copper wire

Wiring requirements:
AC INPUT:

3-Phase, 4 wire plus Ground

AC OUTPUT:

3-Phase, 4 wire plus Ground

DC INPUT:

3 wire (positive, negative and neutral) plus Ground



Maximum cable diameter that terminals can accept.

Refer to torque specifications table for torque requirements.

UPS Model

Rectifier Input

Bypass Input

DC Input

AC Output

GND

LP 33U Series / 10 kVA

4 AWG

4 AWG

4 AWG

4 AWG

4 AWG

LP 33U Series / 20 kVA

4 AWG

4 AWG

4 AWG

4 AWG

4 AWG