Installation Guide LP 33U Series 10 & 20 kVA / S1

3.9 ELECTRICAL CONNECTIONS

WARNING !

The connections to and from the UPS must be executed by QUALIFIED PERSONNEL
ONLY.
Refer to the “Safety prescriptions - Installation
” described in section 1.



3.9.1

Common input utility

Fig. 3.9.1-1 Common input utility

Common input utility

The UPS delivered in standard version has
common input utility.
Only one input line (F1) supplies both rectifier
and bypass input terminals.

Bear in mind that when the utility fuses are
opened there is a supply failure to the rectifier
as well as to the automatic bypass and manual
bypass.


LPS33U

_010-020

_Connec

tion com

mon_01

OFF

OFF

ON

ON

LOAD

X2

1 - INPUT

X1

UTILITY

L1

-1

L2

-1

L3

-1

N1

L1

L2

L3

N2

Fig. 3.9.1-2 Power connections Common Input Utility

Input utility connection
L1-1
= Rectifier + Bypass Phase A
L2-1 = Rectifier + Bypass Phase B
L3-1 = Rectifier + Bypass Phase C
N1 =

Neutral

utility

PE =

Earth

Output load connection
L1
=

Load

phase

A

L2 =

Load

phase

B

L3 =

Load

phase

C

N2 =

Neutral

load

PE =

Earth

load

Max. rating X1 and X2 terminals:

4 AWG (25mm

2

)

NOTE !

For UPS correct operation, the input utility phase rotation must be clock-wise.
Inside the UPS, all neutrals N1
and N2 are connected together.


Connect wire to the Terminals using appropriate tools and appropriate torque.
Torque specification for Input / Output and DC power connections on Terminals: Section 3.8.1.

NOTE !

This UPS is designed to operate in a wye-configured electrical system with a solidly
grounded neutral.