Installation Guide LP 33U Series 10 & 20 kVA / S1

3.9.4

Kit for external battery connection to LP 33U Series / 20 kVA

Before proceeding to an external battery connection, follow the Safety rules concerning the battery.

Make sure that the UPS is not powered, and remove the external battery protections and the fuses F9,
F10, F11
and F13, F14, F15 at the front of the UPS cabinet.

ATTENTION !

Before closing the battery fuses F9, F10, F11 and F13, F14, F15, verify for correct
polarity of the battery connection.


L1

L2

L3

N2

LOAD

X2

X1

L1-1

L2-

1

L3-1

N1

1 - INPU

T UTILI

TY

-

0

+

-

0

+

Bottom entry cables

F9

F10 F1

1

F13 F1

4 F15

X2

LOAD

F9

F10

F11

F13

F14

F15

BATTERY

Red

Re

d

Black

Bla

c

k

Light

Light

b

lue

blue

Battery block diagram

0

+

-

+ 0

-

OFF

OFF

ON

LPS33U_

010-020_

Connectio

n commo

n_01

ON

Fig. 3.9.4-1 Kit for external battery connection to LP 33U Series / 20 kVA


F9 (+)

F13 (+)

= Positive pole

F10 (0)
F14 (0)

=

Central point of
battery blocks

F11 (-)
F15 (-)

= Negative pole


NOTE !

The length of the cables connecting the 3 terminals (X2 - +, 0, -) to the fuses F9, F10,
F11
and F13, F14, F15 must be the same.
Clamp the input battery cables with the included cable-ties.