Installation Guide LP 33U Series 10 & 20 kVA / S1

4.3 EPO (EMERGENCY POWER OFF)

WARNING !

Connections described in this chapter shall be done only by a trained person or
SERVICE ENGINEERS
.


An external Emergency switch (NC - Normally Closed

voltage-free contact) can be connected on terminals X7 / 1,
2
of the P2 – Mainboard.

NOTE !

To enable this function, remove jumper
JP8
on the P2 - Mainboard, when the
cables have been already connected on
X7 / 1, 2
.

LPS33U_

010-020_

UPS EPO

_01

OFF

Q1

Q2

ON

OFF

ON

F1 F2

F3

F13 F14

F15

F9 F10

F11

1

2

X7

P2 - Mainboard

J28

JP8

Fig. 4.3-1 Terminals X7 - EPO

In a parallel system a separate NC
(Normally Closed) contact must be
connected individually to each unit.


When activated, this switch causes the immediate shutdown of booster, battery-charger, inverter; and
the contactors K4, K6 and K7.


NOTE !

This procedure could imply a load shutdown.


When the EPO has been activated, the system must be restored as follows:

Press the push-button EPO (contact on X7 / 1, 2 is closed again).

Press the key O (Inverter OFF – see Section 6.2 of Operating Manual) on the control panel.

Press the key I (Inverter ON – see Section 6.2 Operating Manual) on the control panel.

In case of a Parallel System press the key “O” (Inverter OFF) on the control panel of
each unit connected on the parallel bus and having its output switch Q1 closed.