Installation Guide LP 33U Series 10 & 20 kVA / S1

4.4 CUSTOMER INTERFACE BOARD (OPTION)

WARNING !

The installation and cabling of the options must be performed by
QUALIFIED SERVICE PERSON
.

Serial port J3 - RS232 (sub - D - female 9 pin)

Total remote management of the system using
software GE Power Diagnostics, GE Data Protection or
GE Service Software for system protection and
management of the UPS systems.

Pin 2: TX (out)

Pin 3: RX (in)

Pin 5: GND

J2 (sub – D female 25p) – Output signals on voltage-free contacts

J2 / 1, 2, 3

NO, C, NC

Utility failure

J2 / 4, 5, 6

NO, C, NC

Load on inverter

J2 / 7, 8, 9

NO, C, NC

Stop operation

J2 / 14, 15, 16

NO, C, NC

Load on utility

J2 / 17, 18, 19

NO, C, NC

General alarm (NO)

J2 / 20, 21, 22

NO, C, NC

Buzzer


Signals on terminals X1 and on connector J2 are in parallel and

therefore not separated galvanically from each other.

The programmable signals on X1 and J2 will be disabled with Q1

open, with the exception of the signals for:

16 – Manual bypass ON
24 – Relay output ON

25 – Relay output OFF

26 – EPO


X1 – Output signals on voltage-free contacts

X1 / 1, 2, 3

NO, C, NC

Utility failure

X1 / 4, 5, 6

NO, C, NC

Load on inverter

X1 / 7, 8, 9

NO, C, NC

Stop operation

X1 / 12, 13, 14

NO, C, NC

Load on utility

X1 / 15, 16, 17

NO, C, NC

General alarm (NO)

X1 / 18, 19, 20

NO, C, NC

Buzzer

X2 – Terminals EPO connection (Emergency Power Off)

X2 / 1, 2 or J2 / 12, 25

NC

EPO (Emergency Power Off)

LPS3

3U_C

ustom

er int

erfac

e_01

1

2

3

4

567

89

1

0

1

1

16

15

14

13

12

22

21

20

19

18

17

J3

J2

X1

2
1

JP3

X2

Fig. 4.4-1 Customer Interface

C

=

Common

NO

=

Normally Open

NC

=

Normally Closed

To enable this function, remove jumper JP3 on the Customer
Interface
and the cable on the terminal X2 / 1, 2.

(See Fig. 4.4-1).
Verify if the cable on the terminal X7 / 1, 2 and jumper JP8 on the
P2 – Mainboard
are OFF (see Fig. 4.4-3).


Programmable functions on input contacts

X1/10, 21 or J2/10, 23

Programmable

X1/11, 22 or J2/11, 24

Programmable / Generator ON (NO)