CDT900 Series Touchscreen Programmable Thermostata

Table 14. Troubleshooting. (CONTINUES)

Symptom Possible

Cause Action

Heating equipment failure.

Check for 24 Vac at the equipment on

the secondary side of the transformer

between power and common. If voltage

is not present, check the heating

equipment to find the cause of the

problem.

Check for 24 Vac between the heat

terminal (W) and transformer common. If

24 Vac is present, the thermostat is

functional. Check the heating equipment

to find the cause of the problem.

Heat does not turn on (Heat On is solid in

the display).

Loose or broken wire connection

between thermostat and heating

equipment.

Check for 24 Vac between the heat

terminal (W) and transformer common. If

voltage is not present, check wire

connection (loose or broken) between

the thermostat and the heating

equipment.

Cooling does not turn on (Cool

On is solid in the display)

Cooling equipment failure.

Check for 24 Vac at the equipment on

the secondary side of the transformer

between power and common. If voltage

is not present, check the cooling

equipment to find the cause of the

problem.

Check for 24 Vac between the cool

terminal (Y) and transformer common. If

24 Vac is present, the thermostat is

functional. Check the cooling equipment

to find the cause of the problem.