CDT900 Series Touchscreen Programmable Thermostata

Table 2. Terminal Designation Descriptions.

Terminal Designation

Description

Rc (see Note 1)

Power for cooling--connect to secondary side of cooling

system transformer

R (see Note 1)

Power for heating--connect to secondary side of heating

system transformer

C (see Note 2)

Common wire from secondary side of cooling system

transformer

W

Heat relay

Y

Compressor contactor

G

Fan relay

Y2

Second stage cooling

W2

Second stage heat relay

O/B (see Note 3)

Changeover valve for heat pump systems

AUX

Auxiliary heat relay for heat pump systems

E

Emergency heat relay for heat pump systems

L (see note 4)

Equipment monitor for heat pump systems

S1, S2

Optional outdoor or indoor remote sensor

NOTES:.
1.When sed in a single-transformer system, leave metal jumper wire in place between Rc

and R. If used on a two-transformer system, remove metal jumper wire between Rc and R.

2.Common wire is optional when thermostat is used with batteries.

3. If thermostat is configured for a heat pump system in the Installer Setup, configure

changeover valve for cool (O-factory setting) or heat (B).

4.L terminal is an input (system monitor) when the System mode is in the Heat, Off, Cool or

Auto position. L terminal is a 24 Vac output when System mode is Emergency Heat. Must

connect the 24 Vac Common when using the L terminal. See LCD Indication section for more

details.