CDT900 Series Touchscreen Programmable Thermostata

Table 3.installer Setup Menu. (CONTINUES)

Installer Setup

Number

Installer Setup

Name

Settings Notes

0360

Heat Pump Auxiliary

Lockout

0-no auxiliary heat lockout.

40°F (4.5°C)

45°F (7°C)
50°F (10°C)

55°F (13°C)

60°F (15.5°C)

Shown if electric is chosen for
backup heat source and
outdoor temperature sensor
for control is selected. (See
Advanced Features section for
more information.)

0380

Indoor

Dehumidification

Control

0-No indoor dehumidification control.

1-Dehumidification control activated.

Available on select odels. If
dehumidification control is
activated and auto-
changeover is selected in
Installer Setup Number 0300,
the deadband minimum is
defaulted to 5°F (3°C) in
Number 0310.

0500

Furnace Change

Reminder

0-furnace filter reminder off

1-10 run time days

2-30 run time days

3-60 run time days

4-90 run time days

5-120 run time days
6-365 run time days

Run time based on call for fan.