Technicaldata

6.7.2

electrical data with as-interface bus control

Connections

Circular plug-in connector (M12 x 1, 4-pole)

Operating voltage

29.5 V – 31.6 V DC (according to specification)

Outputs
Max. switching capacity

1 W via AS-Interface

Watchdog function

integrated

Devices without external supply voltage:

Max. power consumption

120 mA

Power consumption input during normal operation

(after current reduction;
valve + 1 end position reached)

90 mA

Devices with external supply voltage:

External supply voltage

24 V ± 10 %

The power supply unit must

include a secure disconnection in
accordance with IEC 364-4-41
(PELV or SELV)

Max. power consumption

55 mA (after current reduction ≤ 30 mA)

Max. power consumption from AS-Interface

55 mA

6.7.3

electrical data with Devicenet bus control

Connections

Circular plug-in connector (M12 x 1, 5-pole)

Operating voltage

11 V – 25 V

Max. power consumption

< 80 mA

Output Pull-in current current

≤ 50 mA

Holding current

≤ 30 mA