37

AS-Interfaceinstallation

10.4.3 connection with multi-pole cable and ribbon cable terminal

As an alternative to the bus connection model with 4-pole circular plug, there is the control head with multi-pole
cable (M12 circular plug) and ribbon cable terminal. The wiring diagram of the circular plug corresponds to the bus
connection of the M12 4-pole circular plug (see "Figure 25" and "Figure 26") and can easily be connected to the
ribbon cable terminal (see “Figure 30”).

Figure 30:

Control head 8691 with multi-pole cable and ribbon cable terminal

handling the ribbon cable terminal

The multi-pole cable features a ribbon cable terminal - with M12 plug-in connector branch circuit - for AS-Interface
cable harness. The ribbon cable terminal contacts the AS-Interface cable harness by means of penetration technology
which allows installation by “clipping in” the AS-Interface cable harness without cutting and without removing insulation.

Screws

M12 plug-in con-
nector branch circuit

Work steps:

Open the ribbon cable terminal
(loosen screws and remove cover)

Insert cable harness conclusively

Close ribbon cable terminal again

Tighten screws
Slightly undo thread-forming screws
(approx. 3/4 turn to the left) and position them on the
existing tapped bore and screw in.

Figure 31:

Ribbon cable terminal

The teach function can now be used to automatically determine and read in the end positions of the valve
(description of the teach function see chapter “10.5 Teach function (calibrating the end position)”).

english