Burkert Type 8691 User Manual

Page 39

Advertising
background image

39

AS-Interfaceinstallation

noTe!

Damage or malfunction due to penetration of dirt and humidity.

To ensure degree of protection IP65 / IP67:

▶ Screw the transparent cap in all the way.

Close the device (assembly tool: 674077

7)

).

Key in recess for actuating the teach function (keep
pressed for approximately 5 seconds

Chronological description of the teach function:

• the bottom end position is read in internally

• the pilot valve switches

• the actuator moves automatically to the top end position

• the top end position is read in internally

• the pilot valve is turned off

• the actuator moves back to the bottom end position

Status LED:
flashes yellow when teach function is running

Pilot valve LED (yellow)

Figure 33:

Teach function

When the teach function is activated the actuator cannot be actuated via the AS-Interface communication.

7)

The assembly tool (674077) is available from your Bürkert sales office.

english

Type 8691

Advertising