8 network topology of a devicenet system, 9 configuring the control head, Dip switches – Burkert Type 8691 User Manual
Page 47
Advertising
47
DeviceNet
11.8 network topology of a Devicenet system
Line with a trunk line and several drop lines.
Trunk lines and drop lines consist of identical material (see diagram).
Trunk line
DeviceNet cable
Terminating
resistor
120 Ω
¼ W
Terminating
resistor
120 Ω
¼ W
Drop lines
DeviceNet cable,
max. 6 m long
T01
Tn
Subscriber 1 (node1)
Subscriber n (node n)
V +
V –
CAN_H
CAN_L
Figure 40:
Network topology, DeviceNet
11.9 configuring the control head
11.9.1 Dip switches
Figure 41:
DIP switches DeviceNet
8 DIP switches are available for configuration:
• DIP switches 1 to 6
for the DeviceNet address
• DIP switches 7 to 8
for the baudrate
english
Type 8691
Advertising