Configuration of the pcb devicenet, 7 terminating circuit for devicenet systems – Burkert Type 8691 User Manual

Page 46

Advertising
background image

46

DeviceNet

11.6.2 configuration of the pcB Devicenet

Valve connection

Internal connection

LED – pilot valve (yellow)
Device status LED (two-colored: red/green)
Bus LED (two-colored: red/green)

DIP switches for
bus address and baudrate

Figure 38:

DeviceNet PCB

11.6.3 Bus connection (circular connector m12 x 1, 5-pole, male)

The control head features a 5-pole micro-style circular connector.

The following configuration conforms to the DeviceNet specification.

pin

1

2

3

4

5

signal

Shielding

V +

V –

CAN_H

CAN_L

Table 14:

Pin assignment circular plug-in connector DeviceNet

Pin 4: CAN_H

white

Pin 5: CAN_L

blue

Pin 1: Drain

(Shield)

Pin 3: V–
black

Pin 2: V+
red

Data lines

Supply voltage
11 ... 25 V DC

max. power 3 W,
if valve is switched

Figure 39:

View of plug from the front onto the pins, the soldered connections are behind

11.7 Terminating circuit for Devicenet systems

When installing a DeviceNet system, ensure that the terminating circuit of the data lines is correct.

The circuit prevents the occurrence of interference caused by signals reflected onto the data lines.

The trunk line must be terminated at both ends with resistors of 120 Ω each and 1/4 W power loss
(see “Figure 40: Network topology, DeviceNet”).

english

Type 8691

Advertising