Installation

7.3

installing the control head Type 8691 on process
valves belonging to series 20xx

Procedure:

1. install switch spindle

Transparent cap

Position indicator

Actuator

Figure 9:

Installation of the switch spindle (1), series 20xx

Unscrew the transparent cap on the actuator.

Using a hexagon socket key, unscrew the orange/yellow position indicator from the inside of the actuator.

Guide element

O-ring

Plastic part
(of the switch spindle)

Puck

Switch spindle

Spindle (actuator)

Figure 10:

Installation of the switch spindle

(2), series 20xx

Press the O-ring downwards into the cover of the actuator.

Manually screw the switch spindle (and the plugged-on guide element) together with the plastic part onto the
spindle of the actuator, but do not tighten spindle yet.

Tighten the guide element with a face wrench

1)

into the actuator cover (torque: 8.0 Nm).

Tighten the switch spindle on the spindle of the actuator. To do this, there is a slot on the upper side (torque:
1.0 Nm).

Push the puck onto the switch spindle until it engages.

1)

journal Ø: 3 mm; journal gap: 23.5 mm