As-interface installation, 1 as-interface connection, 2 technical data for as-interface pcbs – Burkert Type 8691 User Manual

Page 35: 3 programming data, 10 as-interface installation

Advertising
background image

35

AS-Interfaceinstallation

10

as-inTerface insTallaTiOn

10.1 as-interface connection

AS-Interface (Actuator Sensor Interface) is a field bus system which is used primarily for networking binary sensors
and actuators (slaves) with a higher-level control (master).

Bus line

Unshielded two-wire line (AS-Interface line as AS-Interface cable harness) along which both information (data) and
energy (supply voltage for the actuators and sensors) are transmitted.

network topology

Freely selectable within wide limits, i.e. star, tree and line networks are possible. Further details describe the AS-
Interface specification (A/B slave model conforms to the version 3.0 specification).

10.2 Technical data for as-interface pcBs

Supply: via AS-Interface (29,5 V – 31,6 V)

Outputs: 1 valve Y1, max. 1 W, power reduction after approx. 100 ms

with integrated Watch Dog function

Certification: Licence no. 77601 according to version 3.0

10.3 programming data

aS-interface
31 slaves

aS-interface
62 slaves

I/O configuration

B hex (1 input, 2 outputs)

ID code

F hex

A hex

Extended ID code 1

F hex

7 hex

Extended ID code 2

F hex

E hex

Profile

S-B.F.F

S-B.A.E

Table 6:

Programming data

Bit configuration

Data bit

D3

D2

D1

D0

Input

0 Top not reached
1 Top reached

0 Bot not reached
1 Bot reached

Output

not used

0 Pilot valve OFF
1 Pilot valve ON

parameter bit

p3

p2

p1

p0

Output

not used

not used

not used

"0" START teach function
"1" STOP teach function

Table 7:

Bit configuration

english

Type 8691