11.10 configuration of the process data

To transmit process data via an I/O connection, 1 static input and 1 static output assembly can be selected. These
assemblies contain selected attributes combined into one object so that process data can be transmitted collectively
via an I/O connection.

Process data can be accessed

• cyclically in the connection variants "Polled I/O" and "Bitstrobed I/O", with "Change of state", if input values

change, or

• acyclically via Explicit Messages.


The access path for acyclical access is:

class 4

instance 1

attribute 3


With the

Get_Attribute_Single service the input data can be accessed acyclically for reading.

With the

Set_Attribute_Single service the output data can be accessed acyclically for writing.

1 data byte for inputs:
(sensors or initiators)

1 data byte for outputs:
(actuators or valves)

Bit

sensor

Value assignment

Bit

pilot valve

Value assignment

Bit 0

End position

0 Bot not reached
1 Bot reached

Bit 0

Y1

0 pilot valve OFF
1 pilot valve ON

Bit 1

End position

0 Top not reached
1 Top reached

Bit 1... not used

0 always

Bit 2... not used

0 always

Bit 7

Bit 7

Table 17:

Data byte for inputs

Table 18:

Data byte for outputs