Technical data

Type 8025/8035 /

Pulse output

• type
• function

• frequency (f)
• electrical data

• duty cycle
• protection

polarized, potential-free

• NPN/PNP (wiring dependant)
• pulse output, adjustable pulse

value

• 2,5-400 Hz
• 5-36 V DC, 100 mA max.,

voltage drop 2,5 V DC at
100 mA

• 0,5
• galvanically isolated, and

protected against over-
voltages, polarity reversals
and short-circuits

Relay outputs

• operating

• electrical data of the load (non

UL recognized devices)

• electrical data of the load (UL

recognized devices)

• hysteresis, adjustable

thresholds, normally open

• 230 V AC / 3 A

• 30 V AC max. and 42 V peak

or 60 V DC max.

Current output

• response time (10% to 90%)
• max. loop impedance,

12-36 V DC version

• max. loop impedance,

115/230 V AC version

• wiring, version without relays
• wiring, version with relays

4-20 mA, sinking or sourcing
mode (through wiring)

• 5,75 s (default)
• 900 W at 30 V DC, 600 W at

24 V DC, 50 W at 12 V DC

• 800 W 

• 2-wire
• 3-wire

Protection against polarity
reversals

yes

6.6.

specifications of the connected
flow sensor

Sensor input

• signal frequency
• pulse signal (Hall)
• sinus signal (coil)

• 2,5 to 400 Hz
• NPN, open collector
• typical sensitivity of 35 mV peak-

peak, at 252 Hz

Sensor output

• power supply

• 10-34 V DC (V+ subtract 2

V DC), 1 mA max.

English