Wiring

Type 8025/8035 /

8.7.2. Wiring the 8025, wall-mounted version, 115/230 V Ac, with relays

Before wiring the device, obey the instructions of chap. "8.7.1".

Supply

12..36Vdc

NPN SENSOR
1 PULSE INPUT

2 -

3 +

4 NC

SUPPLY

1

2

3

4 PE

REL1

REL2

FLOW SENSOR

FLOW SENSOR

COIL

NPN

COIL SENSOR
1

2

3 NC

4 NC

L+

L-

PE

P-

P+

NC

L+

L-

PE

P-

P+

Iout

PULSE

OUTPUT

Without

With

Relays

230V

L N

230V

T 250 mA

5 6 7 8 9 10

L N

230V

{

7

5

3

8

2

1

A

B

4

6

PE

Switch A : see chap. "8.3.1"

Switch B : see chap. "8.3.3"

marker 7: all the cables must be fitted here
connector 8: connection of the flow sensor

terminal block 1
NC: not connected
L+ (red wire, factory wired)
L- (green wire, factory wired)
PE: wiring of the PE between the main board and the protection board
P-: (brown wire, factory wired)
P+: (white wire, factory wired)
terminal block 2 pe: Shield wiring (green/yellow wire, factory wired)
time-delay fuse 3: fuse to protect the 115 V AC or 230 V AC
power supply
terminal block 4: wiring of the 115/230 V AC power supply
Jumper wire 5: jumper wire to be removed if the 4-20 mA
output is connected
terminal block 6
Terminal 5: 4-20 mA output
Terminal 6: positive 27 V DC power supply, available to energize
an external instrument
Terminal 7: 0V (earth of the power supply available to energize
an external instrument)
Terminal 8: cable shields
Terminal 9: negative pulse output
Terminal 10: positive pulse output

Fig. 40: Terminal assignment of a wall-mounted version, 115/230 V AC, without relays