Burkert Type 8035 User Manual

Page 16

Advertising
background image

16

Installation

Type 8025/8035 /

Install the device on the pipe in such a way that the upstream and
downstream distances are respected according to the design of
the pipes, refer to standard EN ISO 5167-1 and "Fig. 4":

flow direction

50 x DN 5 x DN

40 x DN 5 x DN

25 x DN 5 x DN

20 x DN 5 x DN

18 x DN 5 x DN

15 x DN 5 x DN

With control valve

Pipe with 2 elbows at 90° in 3

dimensions

Pipe with 2 elbows at 90°

Pipe with 1 elbow at 90° or 1

T-piece

With pipe expansion

With pipe reduction

Fig. 4: Upstream and downstream distances depending on the

design of the pipes

Ensure that the pipe is always filled in the section around the
device (see "Fig. 5").

When mounting vertically ensure that the flow direction is in an
upward direction (see "Fig. 5").

Horizontal mounting

Correct

Incorrect

Vertical mounting

Correct

Incorrect

flow direction

Fig. 5: Filling of the pipe

Prevent the formation of air bubbles in the pipe in the section
around the device (see "Fig. 6").