English – Burkert Type 8035 User Manual

Page 41

Advertising
background image

41

Wiring

Type 8025/8035 /

8.6.2. Wiring the 8025, remote version, 12-36 V Dc, with relays

For a wall-mounted version, obey the wiring instructions of chap. "8.7.1".

Before wiring the device, configure the selectors on the electronic board (see chap. "8.3").

Connect the flow sensor to the transmitter according to chap. "8.5".

Supply

12..36Vdc

FLOW SENSOR

COIL

NPN

L+

L-

PE

P-

P+

NC

L+

L-

PE

P-

P+

Iout

PULSE

OUTPUT

Without

With

Relays

NPN SENSOR

1 PULSE INPUT

2 -

3 +

4 NC

SUPPLY

1

2

3

4 PE

REL1

REL2

COIL SENSOR

1

2

3 NC

4 NC

4

6

3

5

A

2

1

B

PE

Switch A : see chap. "8.3.1"

Switch B : see chap. "8.3.2"

terminal block 1
Iout: 4-20 mA output
L+: positive power supply
L-: negative power supply
PE: wiring of the PE between the main board and the protection
board
P-: negative pulse output
P+: positive pulse output

terminal block 2 pe
Wiring of the cable shields

terminal block 3: wiring of relay 1, see chap. "8.4.2"
terminal block 4: wiring of relay 2, see chap. "8.4.2"
connector 5: connection of the flow sensor see chap. "8.5"
Jumper wire 6: jumper wire to be removed if the 4-20 mA output is
connected

Fig. 38: Terminal assignment of a panel-mounted or wall-mounted version, 12-36 V DC, with relays

English