Mounting, Mounting -7 – CONTREX M-Traverse User Manual

Page 22

Advertising
background image

2 - 7

MOUNTING

This section contains instructions for mounting the M–Traverse in the door panel of a
NEMA Industrial Electrical enclosure. The M–Traverse is packaged in a compact 1/2
DIN Vertical Instrument Enclosure that mounts easily in the door of your Industrial
Electrical Enclosure.

To mount the M–Traverse:

1)

The NEMA Industrial Electrical Enclosure that will house the M–
Traverse must conform to the following environmental conditions:

Temperature: 0 - 55 degrees C

(Internal NEMA enclosure temperature)

Humidity: 0 - 90% RH non-condensing

2)

The dimensions for the door panel cutout are 3.65"+ .03" X 7.25 +.03"
(see figure 2-4). Allow two inches of clearance on all sides of the
cutout for mounting clamp attachments, wire routing and heat
convection.

3)

Insert the M–Traverse through the door panel cutout until the gasket
and bezel are flush with the door panel (see figure 2-4).

4)

The mounting clamps can be inserted in the holes that are located
either on the top and bottom or on the sides of the M–Traverse.
Tighten the mounting screws until the M–Traverse is mounted securely
in the NEMA Electrical Enclosure. Do not overtighten.