WIRING

This section contains the input, output and serial communications wiring information for
the M–Traverse. Please read this section prior to wiring the M–Traverse to ensure that
you make the appropriate wiring decisions.

NOTE: The installation of this motor control must conform to area and local electrical

codes. See

The National Electrical Code

(NEC,) Article 430 published by the

National Fire Protection Association, or

The Canadian Electrical Code

(CEC).

Use local codes as applicable.

Use a minimum wire gauge of 18 AWG.

Use shielded cable to minimize equipment malfunctions from electrical noise
and terminate the shields at the receiving end only.

Keep the AC power wiring (J2) physically separated from all other wiring on
the M–Traverse. Failure to do so could result in additional electrical noise and
cause the M–Traverse to malfunction.

Inductive coils on relay, contactors, solenoids that are on the same AC power
line or housed in the same enclosure should be suppressed with an RC
network across the coil. For the best results, use resistance (r) values of 50
ohms and capacitance (c) values of 0.1 microfarads.

Install an AC line filter or isolation transformer to reduce excessive EMI noise,
such as line notches or spikes, on the AC power line.