Direct mode, Direct mode -29 – CONTREX M-Traverse User Manual

Page 76

Advertising
background image

3 - 29

DIRECT MODE

The Direct mode is used to calibrate and troubleshoot the M-Traverse. In the Direct
mode of operation, you can set the level of the Speed Command Out directly from the
M-Traverse to the motor drive. The Direct mode is an open-loop mode of operation.
Therefore, Scaling, Accel/Decel, and closed loop compensation (PI) algorithms are
bypassed in the Direct mode. The Direct mode is used in conjunction with the Run and
the Stop controls.

Caution: To avoid damage to your system, the M-Traverse must be calibrated and the

motor drive set up before you enter the Direct mode. Refer to

Installation/

Setup: Calibration.

The Direct Analog Command (CP-62) parameter uses the full 12 bit resolution of the
analog Speed Command Output.

A value of 4095 is a 100% forward output command.
A value of 2048 is a 50% forward output command.
0 is a zero output command.

A negative value indicates a reverse output command (e.g., - 4095 is a 100% reverse
command).

To enable the Direct mode, enter "2" the Control Mode (CP-14) parameter.

The factory default Direct Mode Control Parameters are found in Table 3-20. To modify
the default parameters, refer to Table 3-21. If you are uncertain how to enter a Control
Parameter, review the

Operations: Keypad

section.

Table 3-22 Default Direct Mode Control Parameters

CP

Parameter Name

Parameter Value

CP-62

Direct Analog Command

0

CP-14

Control Mode

1

Table 3-23 Entering Direct Mode Control Parameters

CP

Parameter Name

Parameter Value

CP-62

Direct Analog Cmd

Enter the DAC bits of the calitrated full scale
Speed Command Out at which you want your
system to operate.

CP-14

Control Mode

Enter “2” to enable the Direct Mode (disables
both Follower Mode options).