CONTREX M-Traverse User Manual

Page 46

Advertising
background image

2 - 31

6)

Put the M–Traverse into RUN by shorting the F–STOP input (J4 pins 9
and 10) and the RUN input (J4 pins 6 and 7). Although the motor is
now in RUN, it will have zero speed until you adjust the Direct Analog
Command (CP-62).

7)

Gradually set the M–Traverse's Direct Analog Command to 90% (3686)
by entering the following on the keypad:

Press “Setpoint”
Enter “400”
Press “Enter”
Enter “800”
Press “Enter”

Continue to gradually increase these increments by 400 until you reach
“3686”. Since there are no acceleration/deceleration ramps in Direct
mode, a sudden increase to “3686” could cause damage in some
systems. If the Follower is not moving in a forward direction, then
rewire the drive/motor leads for forward operation.

Note:

A value of –3686 will change the direction of the motor.

8)

Turn either the motor drive's max speed or the M–Traverse's scale
potentiometer clockwise until the drive motor's RPMs are at the
maximum operating speed at which you want the system to operate.
Check the speed (RPMs) by pressing the Tach” key. “Tach” should
display the RPM speed that you enter in CP-19.

9)

Put the Direct Analog Command back to 0% by entering the following
on the keypad:

Press “Setpoint”
Enter “0”
Press “Enter”

10)

Disable the M–Traverse's direct mode by entering the following on the
keypad:

Press “Code Select”
Enter “14”
Press “Enter”
Enter “1”
Press “Enter”

11)

Put the M–Traverse in “F–Stop” by opening the F–Stop input (J4 pins 9
and 10). Refer to

Installation/Setup: Wiring, F–Stop

.