4 connecting micro-tools to the datalink network – Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual
Page 25
53MT6000 INSTRUCTION MANUAL
Installation 9
4.
Connect the Instrument DataLink cable to the TOP connector at the rear of the SUPERVISOR-
PC card.
3.3.2.4 Connecting Micro-Tools to the DataLink Network
Once a DataLink SUPERVISOR card is installed in the computer, connect the SUPERVISOR card to the
DataLink network using the port provided on the card.
If your controllers have standard rear terminal connections, making this connection requires only one
cable. This cable has a 10-pin connector with a grounding lug on one end and five bare wires on the other.
Cables may be ordered using the part numbers shown in Table 2 in
1.
Plug the 10-pin connector on the cable to the port at the top of the SUPERVISOR card. This
connector is the key to insuring a proper installation.
2.
Connect the connector's grounding lug to the same ground as the DataLink instruments'
power common.
Figure 3-4. SUPERVISOR-PC Jumper Terminal Locations
Table 3-1. Selecting Supervisor Board Base Address With Jumpers J3, J4, and J5
Base
Address
J3
J4
J5
300H
AB
AB
AB
310H
AB
AB
BC
380H
AB
BC
AB
390H
AB
BC
BC
3A0H
BC
AB
AB
280H
BC
AB
BC
290H
BC
BC
AB
J