3 setpoint configurable parameters – Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual

Page 73

Advertising
background image

53MT6000 INSTRUCTION MANUAL

Database Editor 57

7.4.7.3 SETPOINT Configurable Parameters

The control module SETPOINT parameters may be configured by clicking on the SETPOINT button. The
window shown in

Figure 7-12

will be displayed. The database locations where these values are stored for

CON0 are shown in brackets [ ].

Figure 7-12. Setpoint Parameter Configuration Window

ENTRY

EXPLANATION

Tagname:

Tagname of the CON module [A00].

Setpoint Mode:

This parameter selects how the setpoint increase and
decrease pushbuttons function when the Controller is in
remote. Available selections [B338]:
No Effect
Remote SP Ratio - adjusts the Remote Setpoint Ratio
Remote SP Bias - adjusts the Remote Setpoint Bias

Remote Switch:

This parameter is used in conjunction with the Remote
Setpoint Enable to choose between the remote and local
setpoint functions. Available selections [L113]:
Local
Remote

Remote Setpoint Enable: This parameter is used in conjunction with the Remote

Setpoint Switch to choose between the remote and local
setpoint functions. Available selections [L115]:
Disable
Enable