53MT6000 INSTRUCTION MANUAL

Database Editor 67

7.4.10 TOTALIZER Menu

There are eight Totalizer modules that can be configured. The TOT module parameters can be configured
by clicking on the appropriate entry window or button. The window shown in

Figure 7-19

will be displayed.

Any parameter can be selected and changed.

When the TOT button is selected from the Database Editor, a window opens containing the configurable
parameters listed below. The database locations where these values are stored for TOT0 are shown in
brackets [ ].

Figure 7-19. TOTALIZER Configuration Window

ENTRY

EXPLANATION

Module ID:

Selects the Module to be configured. Use the up or down arrow
buttons to cycle through the control module selection.

Tagname:

Tagname (title) of the TOTALIZER MODULE.

Eng. Units:

Engineering Units, up to 10 characters.

DB Input:

Database address of the point to be totaled; for example, C100.
Clicking on the button opens the following display:

Dropout:

To set minimum input value of Module; input values less than this
value will be treated as 0. Clicking on the button opens the following
display: