2 output configurable parameters, Figure 7-11. output parameter configuration window – Micromod Micro-DCI: 53MT6000 Micro-Tools User Manual

Page 71

Advertising
background image

53MT6000 INSTRUCTION MANUAL

Database Editor 55

7.4.7.2 OUTPUT Configurable Parameters

The control module OUTPUT parameters may be configured by clicking on the OUTPUT button. The win-
dow shown in

Figure 7-11

will be displayed. The database locations where these values are stored for

CON0 are shown in brackets [ ].

Auto Enable:

Available selections [L114] :
Auto Disabled
Auto Enabled

Manual Fallback
Disable:

Available selections [L120]:
Fallback Enabled
Fallback Disabled

Process Variable: Displays Process Variable value

Setpoint
(Change):

A setpoint change here only takes effect if controller is in
LOCAL mode [C101]

Output (Change): An output change here will only take effect if the controller

is in MANUAL mode [C102]

Controller Span:

Full scale range in engineering units [C115]

Controller Lower
Range:

Low range value in engineering units [C116]

OK:

Saves changes, closes window and returns to main menu

Save:

Saves changes without closing window

Cancel:

Cancels changes and returns to main menu

Figure 7-11. Output Parameter Configuration Window